NEWS DETAILS

The reason why the air shower room is electrified is not blowing

日期:2024-04-27 00:49
浏览次数:90
摘要:1. If the inlet and outlet doors of the air shower room are not closed properly, the air shower room will not start. Check whether the inlet and outlet doors are closed properly. 2. Check if the door frame and the circular door magnet on top of the door have fallen off or are damaged. The door magnet also sends a signal that the air shower room does not start. Check the door magnet or replace it. 3. Check if the infrared sensing photoelectric sensor is not aligned with the reflector or if th
1. If the inlet and outlet doors of the air shower room are not closed properly, the air shower room will not start. Check whether the inlet and outlet doors are closed properly.
2. Check if the door frame and the circular door magnet on top of the door have fallen off or are damaged. The door magnet also sends a signal that the air shower room does not start. Check the door magnet or replace it.
3. Check if the infrared sensing photoelectric sensor is not aligned with the reflector or if the photoelectric switch is damaged. Just replace it with a new one.
As long as the system prompts and personnel arrangements are followed when using the air shower room, users can quickly complete the purification process within the specified time. Often, the effectiveness of a few seconds of air shower needs to be guaranteed by factors such as equipment quality, daily maintenance, and timely replacement. So, what are the common solutions to the problems encountered when using the air shower room?
If there is an abnormality in the equipment of the wind shower room, it can generally be self checked according to the following methods. If the fault cannot be eliminated, professional personnel can also be contacted for better solutions. The general causes and handling methods of common fault phenomena.
Wind shower room
The fan of the air shower room equipment does not rotate:
1. Replace the fan due to phase loss and burning out;
2. Check for any short circuit or leakage when the incoming air switch trips;
3. Replace the fan if the working time of the fan is too long;
4. The electrical components inside the distribution box are damaged. Replace the damaged electrical components.
5. Is the emergency switch of the outdoor box of the wind shower disconnected. If it is confirmed that it has been cut off, gently press it with your hand and rotate it to the right to release it.
Wind shower room equipment with low wind speed:
1. The initial filter has been used for too long, causing initial blockage and replacing the initial filter;
2. The phase sequence of the three-phase power supply is incorrect. Readjust the phase sequence of the three-phase power supply;
3. The high-efficiency air filter has been used for too long, causing efficient blockage and replacing the high-efficiency filter.
4. Check if the 80V three-phase four wire circuit is installed incorrectly.
Wind shower room inspection
The equipment fan does not stop:
1. Replace the damaged intermediate relay;
2. Replace the time relay if it is damaged.
Equipment lighting not working: The fluorescent lamp is aging, replace it.
Precautions for maintenance of wind shower room equipment:
1. It is strictly prohibited to open the door when the shower or cargo shower room is in a blowing state (until the blowing stops). In case of emergency, you can press the emergency stop switch to stop spraying;
2. After the wind shower room is powered on, the doors on both sides are electronically interlocked. When one side door is not closed, it is strictly prohibited to forcefully open the other side door.
Maintenance methods for wind shower room equipment:
1. It is recommended to replace the primary filter once a month, and the replacement cycle can be appropriately extended or shortened depending on the actual usage situation.
3. When the wind speed of the shower significantly decreases, it is necessary to replace the air filter.
4. Regularly wipe the shower room to maintain internal cleanliness.
The above is the solution to common problems encountered when using an air shower room. To maintain the normal working condition of the air shower room, responsible personnel need to understand the working principle and maintenance methods of the air shower room equipment. They also need to use it in a standardized manner during use, which is beneficial for extending the service life of the air shower room.